2024 Water Quality Report

Stage 2 Disinfectants and Disinfection By-Products

CONTAMINANT & UNIT OF MEASUREMENT

DATES OF SAMPLING (MO/YR)

MCL VIOLATION (Y/N)

Level Detected

Likely Source of Contamination

Range of Results

MCLG MCL

By-product of drinking water disinfection

Haloacetic Acids* (HAA5) (ppb)

1/24 - 12/24

N

44.3

30.8 - 58.5

N/A

60

By-product of drinking water disinfection

Total Trihalomethanes* (TTHM) (ppb)

1/24 - 12/24

N

52.6

43.5 - 66.4

N/A

80

*Reported Locational Running Annual Average (LRAA) is based on results from previous quarters not reported on this table.

Lead and Copper (Tap Water)

No. of sampling sites exceeding the AL

90th Percentile Result

AL (Action Level)

CONTAMINANT & UNIT OF MEASUREMENT

DATES OF SAMPLING (MO/YR)

AL EXCEEDED (Y/N)

Likely Source of Contamination

MCLG

Corrosion of household plumbing systems; erosion of natural deposits; leaching from wood preservatives

Copper (tap water) (ppm)

6/23

N

0.04

0

1.3

1.3

Corrosion of household plumbing systems; erosion of natural deposits

Lead (tap water) (ppb)

6/23

N

3.3

1

0

15